Ask ten suppliers to quote an automatic sliding door with a lock and you will get ten quotations that are not quoting the same thing. Not because nine of them are being dishonest, but because the sentence contains a word that does nine different jobs in this industry, and a second word that describes a state rather than a part. Nobody in the chain is lying. Everybody in the chain is answering a different question.
On a manual sliding door, a lock is a component. You buy it, it goes in the stile, and it does or does not have a bolt in the keep. On a powered door, a lock is a condition the door has been put into. It exists in one mode out of six, under one of two power states, and - if the door happens to be on an escape route - only after a named person has decided something about the building that has nothing to do with the door.
The clearest evidence for this is a single sentence in the user manual of one European sliding door operator. Describing the mode that closes the door at the end of the day, it says: in an escape route the OFF mode may only be set after it is certain that all people have left the building. That is not a sentence about hardware. It is a sentence about a headcount. The mode that locks your door is the only door mode whose lawfulness depends on whether the building is empty, and no lock manufacturer can sell you the answer to it.
What follows is written for the person who has to specify this once and live with it for a decade. We make the aluminium leaf. We do not make the operator, we do not make the access control lock, and we will say plainly which sentences belong to which party.
Before you compare quotations, separate the nine things that get called a lock. Four of them are not locks at all. Two of them are locks that are designed to lose. One of them is a lock on the decision rather than on the leaf. The table below is the index for the rest of the article.
| What the buyer means | What actually holds the leaf | Who supplies it | What it does not do |
|---|---|---|---|
| It shuts at night | Night or OFF-CLOSE mode: the drive closes the leaf, then isolates the activators | Operator | Resist a push. If no locking device is fitted, a closed leaf is not a secured leaf |
| Nobody can come in | Exit-only or one-way: the outside activator is disabled, the inside one stays live | Operator | Lock anything. It is a direction, not a bolt |
| The motor holds it | Gearbox and self-locking drive holding torque | Operator | Survive a power cut as a barrier. It is designed to be back-driven by hand when power is lost |
| It bolts itself | Electromechanical bolt or motor lock built into the operator | Operator, as an option | Throw if the leaf has not finished travelling. The bolt needs an exact closed position, not an approximately closed one |
| It is magnetically held | Electromagnetic lock body plus armature plate | Access control | Hold without power, and it assumes a frame that does not move - which a sliding leaf is not |
| The strike releases | Electric strike or shear lock | Door hardware | Behave the same on a fire-rated door as on a perimeter door. Different rule, different default |
| It has a key | Mechanical cylinder, hook or mortise lock in the leaf stile | Door hardware / leaf supplier | Co-exist with the drive. It is the device the operator manual tells you to release first |
| It opens if you push it | Break-out latch, or mechanical emergency opening on the operator | Leaf plus operator | Reset itself. After it loses, the operator stays inhibited until somebody re-seats the leaves |
| Nobody can change the mode | Key switch, code, or a lockable programme switch | Operator / installer | Lock the leaf. It locks the decision about the leaf, which is a different failure |
Notice that the two rows most buyers are actually asking for - rows one and two - are not locks at all. This is why the phrase sliding door with lock produces quotations that differ by more than the price of a lock: half of them are quoting a mode, and a mode is a software setting in somebody else's controller.
Every powered sliding door has a mode selector. The names differ between manufacturers, which is itself worth knowing, because a buyer who has read one manual will assume the word means what it meant there. We have put two manufacturers' published mode tables side by side below and deliberately not reconciled them. Where they disagree, that disagreement is the finding.
| Mode | What the door does | Is it locked | Are the safety devices working | What the published manual adds |
|---|---|---|---|---|
| Automatic / AUTO | Opens on inner and outer activation, closes after an adjustable time | No | Yes | Two-way traffic. Some manuals let a key impulse open the door partially from this position |
| Reduced opening width / AUTO PARTIAL | Opens to a set fraction of the full travel | No | Yes | One manual says the reduced width may not be less than thirty percent of the opening width, and on emergency exits must be at least the required escape route width. Another says an emergency push-button overrides the partial setting and opens fully |
| Hold open / OPEN | Moves to open and stays there | No | Activation deactivated | One manual notes the leaves can be moved by hand in this mode, for example for cleaning |
| Exit only / EXIT | Inner activator live, outer activator disabled | It depends on the route, not on the door | Partly | The row where two manuals split. One says the door is normally locked in this mode if a locking device is fitted; the same row adds the bracket: unlocked if escape route |
| Night / OFF-CLOSE | Drive closes the leaf, then isolates activation | Only if a lock is fitted - one manual writes the words "if fitted" twice in a single sentence | No | "All activation and safety devices are isolated once the door is fully closed." And, on an escape route, this mode may only be set once it is certain that all people have left |
| OFF / service | Drive and locking switched off, leaves free by hand | No | No | Drive motor and locking are both switched off. This is the mode in which the door is genuinely unlocked and genuinely unguarded |
Two things in that table deserve to be said out loud, because nobody puts them in a quotation.
First: the mode in which you are permitted to lock the door is the mode in which the door stops looking. "All activation and safety devices are isolated once the door is fully closed" is not a footnote. It means the presence sensors that protect people in the doorway during the day are not protecting anything at night. If your night-time risk model assumed the door still had its sensors, it does not.
Second: one manufacturer's display does not show one locked state. It shows two characters - one while the door is travelling to the locked position, one once it has arrived and the lock is confirmed. A two-character display for two states that buyers collapse into a single word is a fair measure of how much is being assumed away.
If a lock were a property of the door, then a power failure would produce one outcome. It does not. At least one European sliding door operator installation manual publishes a whole chapter on mains failure, and the outcome depends on which mode the door was in when the lights went out, whether an emergency battery is fitted, and whether the operator has mechanical emergency opening.
| Equipment fitted | Mode at the moment of failure | What the manual says happens | What that means for the lock |
|---|---|---|---|
| No battery, no mechanical emergency opening | Night / locked | The door remains blocked. You must operate the manual unlocking mechanism before the leaves can be moved by hand | The lock has outlived the power that was holding the door shut. Somebody has to find the release, in the dark, by feel |
| No battery, with mechanical emergency opening | Closed position | The door opens to the open position on power failure | Fail-open is a hardware option. It is not a consequence of buying an expensive operator |
| Charged emergency battery | Night | Door closed and locked. Control unit switches off and wakes on a key command | A charged battery keeps the locked state, not the open one. This is the row that surprises people |
| Charged emergency battery | Automatic | The door keeps functioning normally, or opens, for a period the manual gives as roughly fifteen to thirty minutes | Same door, same battery, opposite outcome - decided entirely by the mode it was in |
There is no honest way to describe a lock as a property of a door that behaves in four different ways on the same event. What you are buying is a set of configured behaviours, and the configuration is done by whoever commissions the door.
The single most misread pair of words in access control. "Fail safe" sounds like the stronger specification. It is the weaker one for your stockroom and the only lawful one for your escape route, because the word safe refers to the person trying to leave, not to the thing you are protecting.
| Question | Fail safe | Fail secure |
|---|---|---|
| What happens when power is lost | The door unlocks | The door stays locked |
| What the word actually refers to | Safe for the occupant | Secure for the asset |
| Typical device | Magnetic lock. It needs power to hold, so no power means no hold | Electric strike. It stays latched until power releases it, unless a fail safe variant is specified |
| Where it is used | Escape routes, stairwells, main entrances, lobbies | Server rooms, storage, pharmacy, rooms that are not a required exit |
| What model codes ask for | Release on fire alarm, on loss of power, and on a manual release at the door - three separate triggers | A mechanical override on the inside is still required in most jurisdictions, so nobody is trapped |
| The cost nobody quotes | Continuous power draw to stay locked, so a battery matters more than people expect | On a fire-rated door, some authorities require positive latching, which pushes you back toward fail secure - and into conflict with the row above |
We are not going to tell you which to choose, and we would distrust any door supplier who does. That is a decision for your fire engineer and your authority having jurisdiction. What we will tell you is the question to ask: is this door on a required escape route, in writing, signed by somebody who owns that decision? Until that is answered, every lock quotation is a guess.
Look at the input and output list of a published sliding door controller and the word lock appears more than once, on separate terminals, doing separate jobs. This is the clearest published proof that a lock is a process and not a part.
| Terminal as published | What it is | Why it decides your outcome |
|---|---|---|
| Lock (output) | Puts the door in the closed position and sends a lock signal if a lock is present | This is a command. Most systems stop here, and report the command as if it were a state |
| Lock position feedback (input) | The terminal the feedback signal of a lock connects to | This is the proof. Without it, your access control dashboard is showing you an intention, not a fact |
| Emergency (input) | Used to unlock the locks in an emergency | This is the release, and it is a separate terminal. Removing the lock command is not the same thing as releasing the lock |
| Fire (input) | Sets the door to an escape-door or fire-door position | In fire-door action the manual states that all electric lock activities are disabled. The fire input outranks the other three |
| Emergency stop (input) | Switches off the electrical drive | Stopping the motor is not unlocking the bolt. During commissioning, test them separately |
There is a matching detail in the service manual of a different class of sliding door operator - the sort used where the consequence of a failed lock is not commercial. It describes adjusting the door position switches so that they change state just as or slightly after the leaf stops moving, but before the carriage finishes its final travel, "allowing the device motor to coast into the full locked position". And then: the device should provide a secure indication only when the door is closed and the lock bar is completely down.
That is the whole problem in one sentence. The mechanical lock completes after the motor has stopped driving. The motor coasts into the lock. If the leaf is a millimetre short - a swollen gasket, a cold morning, a grain of sand in the track - the bolt has nothing to go into, and the system reports "closed" rather than "locked". Your log will say the building was secured. It was not.
Here is the collision that nobody prices in, and it comes straight out of the operator manuals rather than out of anything we invented. One manufacturer prints it as an IMPORTANT NOTICE in block capitals: if manual locks are fitted to the door leaf, ensure they are UNLOCKED before switching the drive into any operational mode, and switch the drive to night mode before locking the door. We found the same notice in two of that manufacturer's manuals, for two different drive families.
Now hold that against our own catalogue. One of the sliding door series we publish - the SL126/182 variant with the seventy five millimetre sash - lists a multi-point locking design with stainless steel locks in precision-cast reinforced casings. That is a real lock, in a real stile, and we are glad it is there. But if that leaf is motorised, that lock becomes precisely the device the operator manual tells you to release first.
| Question | Manual lock in the leaf | Electric lock in the operator |
|---|---|---|
| Who asks for it | The security spec, the insurer, sometimes the tenant | The access control designer, the facilities team |
| What the operator manual says about it | Unlock it before switching the drive into any operational mode | Put the drive into night mode before locking |
| What happens if both are engaged | The drive tries to move a leaf that a bolt is holding. The controller logs an obstruction or a motor fault - not a lock fault | The technician chases a drive problem that is actually a sequencing problem, and may raise the force setting to get past it |
| Who wins by default | Nobody. There is no default. It has to be written down | Nobody. See the row above |
| What we publish that lands here | A multi-point locking design with stainless steel locks in precision-cast reinforced casings, on one sliding door series | Nothing. We do not publish an operator, an operator lock, or an access control device |
The last row of that table is the one that matters most from us. If you are buying a leaf from a system house and an operator from an automation house and a lock from an access control house, then the sentence "who releases what, and in what order, and who proves it" belongs to none of the three. It belongs to the commissioning engineer, and it has to be written down before the leaf is cut.
There is a granted United States patent for an electromagnetic lock assembly for sliding double doors. We are not interested in the invention. We are interested in its background section, because a patent applicant has to describe the problem honestly in order to justify a solution, and what it describes is the most useful published paragraph we have found on this subject.
Read that third bullet again. The reason a magnetic lock is hard to fit to a powered sliding door is not the lock. It is the aluminium above the door. The transom is a cover, and a thin one, and a lock that is asked to resist a pry bar cannot be anchored to a cover.
That is a fabrication decision, and it is the one thing in this whole article that a door system supplier genuinely owns. Reinforcement for a lock body, a machined pocket instead of a drilled hole, a keep plate that is part of the section rather than screwed on afterwards, and a cable raceway that does not require somebody to drill through a transom full of wiring on a ladder. All of those have to be in the extrusion and the machining file. None of them can be added sensibly after the leaf is glazed.
The building side of it is just as unforgiving. One operator installation manual states that the transom must be fastened to a flat surface solid enough to bear the weight of the leaves, that the fastening points must be distributed alternately along the reference lines every three hundred millimetres with M6 or equivalent fixings, and that the transom is not self-bearing. A lock that holds a leaf still is asking the structure behind the transom to take a load in a direction the operator never asked for.
We publish a specification table for each sliding door series. Almost none of it is about locking, and the parts that look relevant are usually measuring something else. Here is the honest reading, including the two places where our own table is easy to misread.
| What we publish | Values across the sliding door series | What it actually measures | What it does not tell you |
|---|---|---|---|
| Frame wall width | 112 / 126 / 155 / 167 / 182 mm | How far the outer frame goes into the wall | Not the cavity inside the head for an operator. Not a statement that any operator fits. Ask for the transom section drawing |
| Glass sash thickness | 43 / 54.5 / 55 mm | The stack of the sash, front to back | Not the glass rebate. Do not infer a glazing thickness from it, and do not infer a lock body depth from it either |
| Sash width | 44.5 / 53 / 75 / 96 mm | The visible face of the sash - and therefore the room a lock body has | Nothing about strength or reinforcement. A narrow sash and a serious lock are in direct competition for the same millimetres |
| Frame width | 26 / 36 / 62 mm | The visible outer frame | Nothing about locking. This is the number that gets quoted in a brochure, and it is not the number that decides whether the lock fits |
| Pulley load capacity | 400 kg, twenty-wheel self-balancing, on one series | What the rollers carry, per sash | Not the driving capacity. These two numbers are not the same measurement |
| Driving capacity | 220 kg, on another series | What the gear is rated to move, per sash | Not the load capacity. Putting 400 and 220 in one column and sorting descending is the single most common way this catalogue is misread |
| Track height | Low 8 mm, high 43 mm, high-drop 45 mm plus an optional 85 mm water barrier | The threshold decision, and the water line | A locked door still has to drain. The threshold, the floor guide and the lock are decided on the same drawing, not in three meetings |
| Multi-point locking | Stainless steel locks in precision-cast reinforced casings | A real mechanical lock in a real stile, on one series | It is a manual lock. On a motorised leaf it becomes the device the operator manual tells you to release first |
| Thermal K value | 1.3, on a window series | A system thermal value for that window | Not a door value, not a whole-unit value, not an NFRC value. Nothing to do with locking, and it does not transfer to the door series |
| Salt spray and shear | 240 hours and 5000 N, on a window series | Coating and substrate corrosion, and the composite bond between the insulation strip and the aluminium | Neither is a lock rating, neither is a cycle rating, and neither transfers to the other series. A lock that survives them tells you nothing |
| Maximum single sash | 2800 by 2600 mm on one series, 2500 by 3000 mm on another | The largest leaf we list, under an assumed glass configuration | The leaf mass, which is what the operator is sized against. A heavier glass build changes both the mass and the maximum |
If you take one row away, take the sash width row. The number that gets quoted back to you in a brochure is the frame width. The number that decides whether the lock you have specified will physically go into the door is the sash width, and on our narrowest published sliding door sash that is forty four and a half millimetres. A security sliding door is not a product category; it is a set of decisions about which millimetres go to the sight line and which go to the hardware.
Everything above assumed one door. In practice there are two doors with identical hardware and opposite lawful behaviour, and the difference is a decision made on a fire strategy drawing by somebody who never sees the quotation.
| The same piece of hardware | Door not on an escape route | Door on an escape route |
|---|---|---|
| Exit-only mode | "The door is normally locked ... if an electromechanical locking device has been fitted" | "unlocked if escape route" - the same sentence, same switch, opposite outcome |
| Night / OFF-CLOSE mode | Closed and locked, if a lock is fitted | May only be set once it is certain that all people have left the building |
| Programme switch | Anybody can change the mode | Must be secured against operation by unauthorised persons - key, code or a lockable switch. One manual adds that the key must always be removed after changing settings |
| Break-out versus redundant operator | Optional | One of the two is required. A European reading of EN 16005 describes the non-break-out type as having to open at least eighty percent of a two metre opening within three seconds of activation, or within five seconds of power loss, and to be durability tested to at least one million cycles |
| Locking at all | Your call, subject to local rules | Permitted, but the same reading of EN 16005 says it may only be done by key or code - that is, only by authorised personnel |
| Who decides which column you are in | You | Your fire engineer and your authority having jurisdiction, in writing, before you order |
That last point about key or code deserves emphasis, because it is the least known and the most useful. A European reading of EN 16005 does not ban locking a powered sliding door on an escape route. It restricts how you get into the locked state. A time clock that locks the entrance every night at eight is a very normal thing to specify and, on that reading, the wrong thing to specify. What is wanted is a deliberate act by a person who is accountable for the building being empty.
Once you accept that locking is a mode and not a part, a second lock appears in the specification: the lock on the mode selector. One manufacturer's published brochure states that automatic sliding doors in escape and rescue routes must be secured against operation by unauthorised persons, and offers a lockable mechanical switch, a key switch, or a code. Another's user manual adds the small, hard instruction that the key must always be removed from the mode selector on emergency escape doors after changing the settings.
Nobody quotes for this. It is a few pounds of hardware and it is the difference between a locked entrance and a locked entrance that a passer-by can unlock by pressing a button. If it is not in the schedule, it will not be on the wall.
On an escape route, one of two things must be true: either the leaves can be pushed out of their track, or the operator is of a type that opens them on power failure without being pushed. Both are locks designed to lose, and the cost of losing is not nothing.
A published guide to resetting a break-out door makes the point that a break-out reset is not a power reset. Cycling the supply does not restore a door that a break-out switch has told the controller is no longer in its normal running configuration. The leaves have to be re-seated, the latches re-engaged, the break-out switch cleared, and the sequence followed - and the sequence is manufacturer-specific, so a generic button combination can create a second fault. The same guide's list of when to stop and call an engineer is short and worth reading before the day you need it.
The practical instruction for a facilities team is simple and almost never written down: put the reset procedure and the responsible person in the handover file, not in the service contract. A door that has been broken out and left inhibited is a door that is neither automatic nor locked, and it will sit like that until somebody notices.
The winter setting is the most harmless-looking feature in the whole controller and it has a number attached. One operator manual states that the reduced opening width may not be less than thirty percent of the opening width, and that in emergency exits the reduced opening width must be at least as large as the required escape route width. Another states that with an emergency push-button a partially opening door opens fully.
So the sequence is: somebody sets a winter opening to save heating, the leaf now opens to a fraction of its travel, and the escape capacity of the entrance has changed without anybody touching the door. If the entrance is a required exit, that setting is a fire strategy input, not a facilities preference. Write it into the commissioning record and lock the mode selector.
| What we can do | What we cannot do |
|---|---|
| Supply the thermal-break aluminium leaf and transom section, in 6060-T66, to the sections we publish | Supply, size or commission the operator. That is a separate supplier with its own declaration |
| Factory-machine the lock pocket, the keep and the cable raceway, so nobody drills a transom on a ladder | Supply or commission the access control lock, or tell you whether it should be fail safe or fail secure |
| Add reinforcement where the lock and the transom need it - decided at order stage, not on site | Be the applicant for the escape route or fire approval in your jurisdiction. That approval is not ours to hold |
| Issue the section drawings your operator supplier needs, with the real numbers on them | Sign the declaration of conformity for the door as a machine. That sits with whoever installs and commissions it |
| Glaze to the agreed configuration and record the resulting leaf mass per unit, which is what the operator is sized against | Tell you the door is compliant. Compliance is a property of the complete installation on your site, not of a leaf in a crate |
We would rather say that than let you build a schedule on a sentence we cannot support. Our published catalogue is four manual sliding door series. If your project needs a powered entrance, the honest shape of the supply chain is: a leaf from us, an operator from an automation house, a lock from an access control house, and one named person who owns the sequence.
Most of the failures described in this article happen because a question was never asked, not because an answer was wrong. Send these twelve lines to every supplier in the chain - leaf, operator and lock - and compare what comes back. The last column is the one that saves you.
| Ask | A useful answer looks like | An answer that sounds reasonable and carries no information |
|---|---|---|
| 1. Is this opening on a required escape route | A named document, a named author, a date | "It should be fine" |
| 2. Which of the nine devices holds the leaf | A device type and part number, not a mode name | "It locks automatically" |
| 3. Fail safe or fail secure | One word, plus the reason, plus who signed it off | "Heavy duty locking" |
| 4. What happens on loss of mains power | One row per mode, stating the outcome for each | "There is a battery backup" |
| 5. What releases the lock on fire alarm | The terminal name, the relay, and the test method | "It interfaces with the fire system" |
| 6. Is there a lock position feedback signal | Yes, with the terminal and how it is reported | "The system shows door closed" |
| 7. Is there a separate emergency unlock input | Yes, and it is not the same terminal as the lock output | "You can switch it off" |
| 8. Where does the lock body sit, in millimetres | A section drawing with the pocket, the keep and the reinforcement marked | "It fits the standard profile" |
| 9. Who releases the manual lock, and when | A named role and a step in the daily procedure | "The staff know" |
| 10. Is the programme switch secured | Key, code or lockable switch, and where the key lives | "It is behind the counter" |
| 11. Break-out or redundant operator | Which one, and the reset procedure in the handover file | "It opens in an emergency" |
| 12. Leaf mass with the agreed glass | Kilograms per leaf, written on the order, per unit | "Standard double glazing" |
| Item | Do we publish it | Why the gap exists | What to do instead |
|---|---|---|---|
| Frame wall width, sash width, sash thickness, frame width | Yes | No gap | Use them, but use the sash width for the lock question, not the frame width |
| Operator compatibility | No | We do not make operators and have not tested against a specific one | Send our transom section to your operator supplier and get the answer in writing from them |
| Lock holding force or attack rating | No | We do not make locks. A number printed by us would be a claim about somebody else's product | Get the rating from the lock manufacturer, against the standard you are actually being assessed to |
| Cycle rating for the powered assembly | No | Any number we could give would be a component number, not an assembly number | Ask the operator supplier for the assembly figure, and ask which standard and which test specimen it came from |
| Thermal K value on the door series | Not on the sliding door series | A sliding leaf has to keep a running clearance, so it seals by contact rather than by compression | Ask for a calculated value for your exact size and glass build, under a named standard. Not publishing it does not mean it is worse |
| 240 hours salt spray, 5000 N shear | Yes, on one window series | They measure coating and the strip-to-aluminium bond, and they are series specific | Do not carry them across to a door. Neither is a lock rating and neither is an air, water or wind class |
| Escape route approval for your project | No | We cannot hold it. It is granted to an applicant for a specific installation in your jurisdiction | Name the applicant in the contract. We can supply sections, drawings and test evidence; we cannot be the applicant |
| Transom fixing pattern and substrate | No | It depends on your wall, and the operator's manual is the authority | Take the fixing centres and the "not self-bearing" note from the operator manual to your structural designer before the opening is built |
Yes, in the European reading we have cited, and the restriction is on the method rather than on the fact of locking: it may be locked only by key or code, meaning only by an authorised person. What is not acceptable is a lock that would hold against someone trying to leave, and what is not acceptable in most jurisdictions is getting into the locked state by a clock rather than by a decision. Your authority having jurisdiction is the only body that can answer for your building.
The published background of a granted patent on exactly this problem says these locks are seldom installed on powered double sliding doors, for two reasons that will still be true on your door: both leaves move, and the aluminium panel above them is thin and gives the lock little support. There is also the drilling problem - the same source warns that the electronics can be damaged during installation. If you want to do this, the reinforcement should have been designed into the section. It is a much cheaper conversation before the leaf is made than after.
Because it is reporting a command rather than a state. A published controller has separate terminals for the lock output, the lock position feedback input, and the emergency unlock input. If the feedback is not wired and monitored, the system is showing you what it asked for. The related failure is mechanical: on one service manual the lock completes after the drive has stopped and the motor coasts into the locked position, so a leaf that stops a millimetre short closes but never locks.
Exit-only is a direction. The outside activator is disabled and the inside one still works, so the building empties and does not fill. It is not a bolt, and one manufacturer's manual makes the distinction explicit by saying the door is normally locked in that mode if a locking device has been fitted - and unlocked if it is an escape route. The same switch position, two opposite behaviours, decided by a drawing you have probably never seen.
No, and this is stated plainly in at least one operator manual: all activation and safety devices are isolated once the door is fully closed in night mode. That is the point of the mode - the door is shut and not cycling. But it means any assumption that the doorway is still monitored outside opening hours is wrong, and it is another reason the decision to enter that mode should belong to a person rather than to a timer.
Because a break-out is not a power event. A published reset guide makes the point that cycling the supply does not clear it: a break-out switch has told the controller the door is no longer in its normal running configuration, and the leaves, latches and operator all have to be returned before the controller will accept a reset. The sequence is manufacturer specific. Put it in the handover file with a named person against it.